Nonmetallic-Sheathed Cable Type NM-B

Feature:
INQUIRY
DESCRIPTION
APPLICATION
Type NM-B (nonmetallic-sheathed cable) may be used for both exposed and concealed work in normally dry locations at temperatures not to exceed 90°C (with ampacity limited to that for 60°C conductors) as specified in the 2011 National Electrical Code. NM-B cable is primarily used in residential wiring as branch circuits for outlets, switches, and other loads. NM-B cable may be run in air voids of masonry block or tile walls where such walls are not wet or damp locations. Voltage rating for NM-B cable is 600 volts.
Standards:
Type NM-B cable complies with:
• ASTM B-3 and B-8
• UL Standard 83
• UL Standard 719
• Federal Specification A-A-59544
• National Electrical Code, NFPA 70. 2011 Edition
• RoHS/ REACH
Features
Nonmetallic-Sheathed Cable. 600 Volt.
Copper Conductors. Color-Coded Jacket.
Four Conductor Available With Two Neutrals.
SPECIFICATIONS
ROHS
ROHS
Low Voltage
Low Voltage
Working Temperature 90℃
Working Temperature 90℃
Flame Retardant
Flame Retardant
CONSTRUCTION
Type NM-B cable is manufactured as 2, 3, or 4 conductor cable, with a bare ground wire. Copper conductors are annealed (soft) copper. Stranded conductors are compressed stranded. Conductor insulation is 90°C-rated polyvinyl chloride (PVC), nylon jacketed. Type NM-B is designed for Easier Pulling, Resulting in Easier installation. The cable jacket is color-coded for quick size identification; White - 14 AWG, Yellow - 12 AWG, Orange - 10 AWG, and Black - 8 AWG and 6 AWG.
1. Jacket:
PVC, flame retardant. 90℃.
2. Assembly:
the conductor laid parallel, with kraft paper tape wrapped.
3. Wrapping:
kraft paper tape over the grounding conductor
4. Core Jacket:
Nylon
5. Insulation:
PVC, type THHN.
6. Conductor
annealed copper, comply to ASTM B3
PARAMETER
Type NM-B Cable
ConductorGround WireApprox. Cable Dimension (mils)Approx. Net Weight per 1000' (lbs)Allowable Ampacity+
Size (AWG)Number of ConductorsNumber of StrandsInsulation Thickness (mils)Size (AWG)Number of Strands
TWO CONDUCTOR
142119141360X1625715
122119121410X1798220
102124101494X21012430
82735101612X26918640
62735101683X30422555
THREE CONDUCTOR
1431191413077415
12311912134710720
10312410142216430
8373510156525340
6373510165035755
437468181456070
237468195281695
FOUR CONDUCTOR
142/21*191413369115
1441**191413369115
122/21*1912138113220
1241**1912138113220
10412410146520130